SKU: CJ1W-IA111

Omron CJ1W-IA111 CJ Series AC Input Unit 16-Points 100-120VAC

Omron CJ1W-IA111 is a 16-point AC input unit for CJ series PLCs, accepting 100-120VAC input signals for industrial automation.

USD 88.00 per unit, volume discounts available

  • In stock, ships in 24h
  • 100% genuine Omron
  • 1-year manufacturer warranty
  • Worldwide delivery

Key Features

  • 16 AC input points
  • 100-120VAC input voltage
  • 50/60Hz operation
  • Individual LED status indicators
  • 40-pin connector interface
  • 15ms response time
  • Noise filtering and debounce
  • DIN rail mounting
01 / Overview

Omron CJ1W-IA111 Digital AC Input Module

The Omron CJ1W-IA111 is a 16-point AC input module designed for CJ1 series programmable logic controllers, providing reliable interface for 100-120VAC control signals. This module is essential for applications where field devices such as pushbuttons, limit switches, and selector switches operate on standard AC control voltage, eliminating the need for external signal conversion. The CJ1W-IA111 features 16 individual input points, each with built-in LED status indicator for easy troubleshooting and maintenance. The module accepts 100-120VAC input signals at 50/60Hz, making it suitable for North American control systems and applications using standard AC control voltages. The input circuitry includes filtering and debounce protection, ensuring reliable detection of mechanical switch contacts while rejecting electrical noise common in industrial environments. The module connects to field wiring through a standard 40-pin connector, providing secure and organized wiring connections. The CJ1W-IA111 has a fast response time of 15ms maximum, suitable for most discrete control applications where high-speed response is not critical. The input impedance and current draw are optimized to ensure reliable operation with a wide range of field devices while minimizing power consumption. The module mounts directly to the CJ1 backplane, drawing operating power from the PLC power supply unit. Applications include machine tools, assembly equipment, packaging machinery, and any application requiring interface to AC-powered control devices. The module robust design and proven reliability make it a standard choice for industrial control systems using AC control voltage.

Typical Applications

  • Machine tool control panels
  • Assembly equipment interface
  • Packaging machinery
  • Material handling systems
  • Process control interfaces
  • Building automation
  • HVAC control systems
  • General industrial automation

Buying Checklist

  • Direct interface to AC control devices
  • Individual status indication for troubleshooting
  • Proven reliability in industrial environments
  • Standard CJ1 series compatibility
  • Easy wiring with connector system
  • Built-in noise filtering
  • Genuine Omron quality
  • Wide availability and support
02 / Specifications

Technical Specifications

Technical specifications for Omron CJ1W-IA111 CJ Series AC Input Unit 16-Points 100-120VAC
ModelCJ1W-IA111
SeriesCJ1W
TypeAC Input Unit
Input Points16 points
Input VoltageAC100-120V 50/60Hz
ON VoltageAC80V minimum
OFF VoltageAC30V maximum
Input Current7mA typical at 110VAC
Response Time10ms (at 50Hz), 8ms (at 60Hz)
Common8 points/common, 2 circuits
ConnectionRemovable terminal block
Current Consumption100mA at 5VDC (internal)
MountingCJ series backplane
Operating Temperature0 to +55°C
03 / FAQ

Frequently Asked Questions

When should I use AC input vs DC input?

AC input: when field devices use AC power (limit switches with AC rating, existing AC wiring). DC input: most common for modern sensors, faster response, lower power consumption.

What's the response time?

10ms at 50Hz, 8ms at 60Hz. Slower than DC inputs due to AC cycle detection. Suitable for most industrial applications but not for high-speed counting.

Can I use this for 220VAC input?

No, IA111 is for 100-120VAC only. For 200-240VAC input, use CJ1W-IA201 (220VAC input unit). Using wrong voltage can damage unit.

How many commons does this unit have?

2 commons (8 points each). Allows grouping inputs by voltage source or function. Each common can be wired to different AC sources if needed.

Need CJ1W-IA111 pricing or lead time?

Email sales@hyx-automation.com or send your inquiry via the form. We respond same business day.